Weekly generator inspection log

The 16 weekly checks for an emergency power supply system, the readings to record, and a printable version for your EPSS binder.

Checklist

16 checks, once a week

Mark each item OK, deficient (X) or not applicable. Log anything marked X and call JRC for anything you can't correct the same day.

Weekly emergency power supply system inspection items
ItemWhat to check
Engine & fluids
01Engine oil at operating level, no leaks under or around unit
02Coolant at correct level, no leaks, cap secure
03Fuel supply adequate, no leaks at lines, fittings or tank
04Belts and hoses, no visible cracking, fraying or looseness
05Air filter restriction indicator not in red, filter clean
Battery & charging
06Terminals clean and tight, case free of cracks or corrosion
07Charger energized, charge rate normal (record volts below)
08Electrolyte at proper level (mark N/A if sealed battery)
Controls & switchgear
09Generator control switch in AUTO
10Control panel clear, no alarm or warning lamps lit
11Main output breaker closed and not tripped
12Transfer switch in normal/auto position, remote annunciator clear of alarms
Environment & access
13Block heater working, engine warm to the touch when at rest
14Room above 40°F, louvers, dampers and vents unobstructed
15Exhaust system intact, no visible leaks, rain cap in place
16Access clear, nothing stored in the room or within clearances

Readings to write down each week

  • Hour meter (hours)
  • Fuel level (% or inches)
  • Battery (volts DC)
  • Coolant temperature (°F)
  • Room temperature (°F)
  • Inspector's initials

Deficiency log

For every item marked X, record: date found, week, item number, what was found, who it was reported to, date corrected, and initials.

Printable version

The same log on one page with space for 13 weeks.

Download PDF (182 KB)